+ BUT… VECA: an integrated approach to prevent aerosol corrosion in data centers

N/A
N/A
Protected

Academic year: 2021

Condividi "+ BUT… VECA: an integrated approach to prevent aerosol corrosion in data centers"

Copied!
1
0
0

Testo completo

(1)

CONCLUSION

The study of aerosol Hygroscopicity coupled with aerosol concentration and thermodynamic studies allowed to find the best conditions to use a DIRECT FREE COOLING in a computer center.

This approach allowed to design a cooling system able to save up to 60% of energy compared to classical conditioning systems.

E. Bolzacchini1, L. Ferrero1, G. Sangiorgi1, M.G. Perrone1

1POLARIS Research Centre, Department of Environmental Sciences, University of Milan - Bicocca, Milan, I-20126, Italy contact author: luca.ferrero@unimib.it

 SAMPLING SITE: SANNAZARO DE’ BURGONDI

(PAVIA) in the middle of the Po Valley, Italy near one of the largest power-plants of Italy

 SAMPLING CAMPAIGN: PM0.4 + PM1 + PM2.5 + OPC-Tandem System (OPC”dry”+OPC”wet”) + Meteo Parameters

SPRING: 10 June – 2 July 2010; SUMMER: 24 March – 29 April 2010

SUMMER

Very similar pattern of ionic balance for both the seasons and all the PMx: R2 very high (R2

0.96); slope very close to 1 (slope ≥ 0.85). The neutrality condition of aerosol prevent the computer damage due to acidity.

However is very important to assess the aerosol hygroscopicity to prevent any corrosion problem due to the overcoming of the Mutual Deliquescence Relative Humidity (MDRH) of aerosol.

OBJECT OF THE STUDY: DATA CENTER (5200 m2

of computers) characterized by a DIRECT FREE COOLING DESIGN

Energy saving depends on external climatic conditions but it can reach values as high as ~50% compared to other cooling techniques (indirect or using common conditioning systems)

Milano Torino

Sannazaro de’ Burgondi

BUT…

…Aerosol that comes into the computer center during the DIRECT FREE COOLING can damage the computers due to their: • Chemical effects (corrosion…)

• Mechanical effect (prevented the dissipation of heat…) • Electrical effects (arc effect…)

THUS… international technical committee (ASHRAE) have given the limits on:

aerosol number concentration (in function of size: ISO8 standard), temperature (15-32°C) and relative humidity (20-80%) to prevent aerosol contamination and aerosol hygroscopicity… thermodynamic limits have to be adapted to the aerosol hygroscopic properties of the air entering in the system.

DIRECT FREE COOLING

means that external air is directly used to cool the

computer center.

Power Plant

Data Center

Mobile Laboratory Power Plant

Concentrazione media oraria - Periodo 1

0,E+00 1,E+07 2,E+07 3,E+07 4,E+07 5,E+07 6,E+07 7,E+07 8,E+07 0 4 8 12 16 20 24 # /m 3 >0.5 um ISO Class8

High Pollution levels (aerosol concentrations above ISO8 standards) need for an aerosol chemico-physical characterization…

 ANALYSIS: PTFE filters extracted in ultra-pure water by ultrasonic bath and analyzed by IC (Dionex® ICS90 and ICS2000 coupled system).

7.4% 17.2% 7.5% 0.3% 0.6% 0.4% 0.5% 66.2%

PM1

SPRING

water soluble inorganic ions

Na+, NH

4+, K+, Mg2+, Ca2+, F-, Cl-, NO3-, PO43-, SO

4

2-mono-/dicarboxylic acids

acetic, propionic, formic, glutarric, succinic, malonic, maleic, oxalic acids

+

y = 0.966x - 0.003 R² = 0.998 0.000 0.050 0.100 0.150 0.200 0.250 0.000 0.050 0.100 0.150 0.200 0.250 M o l + (u m o l/ m 3 ) Mol- (umol/m3)

Ionic balance PM1 - Spring

 AEROSOL HYGROSCOPICITY: Aerosol Inorganic Model (E-AIM), an aerosol thermodynamic model that can simulate aerosol water content, free acidity (free H+), and activities of ionic species in aqueous aerosols and the solid- and liquid-phase compositions (Clegg et al.,

1998; http://www.aim.env.uea.ac.uk/aim/aim.php) 0 5 10 15 20 25 30 35 40 45 0 20 40 60 80 100 H 2 O ( m g /m 3 o m m 3 /c m 3 ) RH%

Daily trend of PM1 Hygroscopicity

PM1 00-08 PM1 08-16 PM1 16-24

AEROSOL CHEMISTRY + THERMODYNAMIC CONDITIONS MDRH 0 10 20 30 40 50 60 70 50 55 60 65 70 75 80 F re q u e n c y % M D R H MDRH (%) Winter PM2.5 Summer PM2.5 Winter PM1 Summer PM1

Frequency distribution of MDRH + external air thermodynamic condition allow to find the best thermodynamic range (the green one in the psychrometric table) to use the DIRECT FREE COOLING

9.3% 6.3% 18.1% 0.3% 0.6% 0.4% 1.1% 63.9%

PM1

PM0.4

NH4+ NO3- SO42- Cl-minor ions monocarb. dicarb. other T (°C) RH % T (°C) RH % PM2.5 12±5 72±19 21±5 72±17 PM1 12±4 72±18 23±5 69±15 PM0.4 12±1 77±9 26±1 61±3 SPRING SUMMER

Riferimenti

Documenti correlati

 spread of competences in stakeholders and agents of change in Alpine remote areas on adaptation to the coming changes or orientation of local opportunities for the labor market

Therefore, this model represents a useful, easy way to correct data measured with GSS sensors to return “FRM-like” ozone concentrations by including two variables easily

To further examine the utility of the differential PSCF (DPSCF) plots, county-by-county emissions data for NH 3 , NO x , SO 2 , anthropogenic VOCs, and primary PM 2.5 have

This evidence suggests that the construction of the pier has altered the morphological equilibrium of the Lignano tidal inlet determining the development of the rapid and

N.B.: This is the PREPRINT (submitted) version of this article. The experimental Nusselts are then compared to pure nucleative and convective heat transfer, once data

Here we used neurosecretory mouse chromaffin cells of the adrenal gland for testing the effects of CdSe eZnS coreeshell quantum dots (5e36 nM) on Ca 2þ channels functionality and Ca

Durante il percorso di dottorato, a seguito dell’analisi delle tecnologie per la cogenerazione tradizionale, sono state prese in esame diverse altre soluzioni per