Coverage of energy for the preparation of hot tap

water by installing solar collectors in a

single-family building

Aleksander Starakiewicz1,*

1Rzeszow University of Technology, Department of Building Engineering, Al. Powstańców Warszawy 12, 35-959 Rzeszow, Poland

Abstract. The paper presents the results of experimental studies on the consumption of hot water, energy obtained from the solar installation in the production process and the degree of coverage of usable and final energy with solar collectors. Thermal energy measurements from solar collectors cover the measurement period from 2011 to 2017. During this period, the annual final energy obtained from solar collectors ranged from 1033–1576 kWh. Monthly and annual demand for usable and final energy for the demand for hot water is presented depending on the amount of hot water used. Monthly actual consumption of hot water in the measurement period ranged from 3.57–9.16 m3. During this period, the number of residents has changed from 3 to 5 people. Annual coverage of energy useful for heat and energy by solar panels in the years 2011–2017 fluctuated from 38.0%–63.9% and 25.2%–42.3% for final energy. Monthly energy coverage ranged from 5.5% to over 100%. Covering energy above 100% in practice means getting a higher temperature of hot water in the outlet valve than expected.

1 Introduction

In buildings equipped with a domestic hot water installation (DHW), it is consumed daily by users for various living needs. The amount of hot water consumed by residents depends mainly on their number, but also on the age of the people, their personal needs, habits, metering, the number of home appliances consuming hot water, equipment classes and the general desire to make savings. Every amount of hot water consumed requires a number of devices for its preparation, storage and distribution. Each of the mentioned types of devices has its own type of energy efficiency (production, storage, distribution and use) affecting the final amount of energy necessary to prepare hot water with the assumed parameters. We are therefore faced with usable thermal energy (Qw,nd) for the preparation of hot tap water and the loss of energy resulting from the efficiency of the devices throughout the system. Energy for heating hot water is produced by single- or dual-function boilers, instantaneous heaters, storage heaters, compact heat centres, heat pumps, solar collectors and geothermal installations. The loss of energy (heat loss) is mainly related to the efficiency of the domestic

(2)

hot water installation, that is its production, storage (storage tank insulation class), distribution (type of insulation of distribution and circulating pipes, circulation work time per day) and use (% age consumption of the prepared hot water volume). Ultimately, knowledge of the usable energy and efficiency of the installation allows us to determine the final energy.

In contrast, devices that produce energy to heat hot tap water can be supplied with various fuels, such as electricity, natural or liquid gas, coal, coke, wood, fuel oil, geothermal energy, biofuel or solar. Thermal energy obtained from the said fuels is burdened with a certain production cost. Expenses borne by the residents related to the consumption of heat and power are generated by the aforementioned factors. Each user is interested in incurring the lowest possible costs, and periodically even zero. This goal can be realized for many months of the year, using a hot tap water heating installation with solar collectors. The following chapters present the actual consumption of hot tap water in a single-family house in a period of 7 years, the amount of thermal energy acquired by solar collectors as well as monthly and annual coverage of usable and final energy generated by the solar collectors.

In the single-family building in Warsaw under consideration, hot water was prepared centrally and accumulated in a bivalent tank with a capacity of 300 litres. The tank has an additional heater and two coils, where the lower one is supplied from the solar system and the upper one (if necessary) from a central heating boiler. The solar installation consists of two collectors with a total active absorber area of 4.70 m2. The collectors are directed to the south and set at an angle of 55º to the level [1]. In 2013, the hot water installation was modernized by installing an additional 70-litre tank. This acts as a buffer tank performing two functions. First of all, it stores some of the hot water with a higher temperature for so-called unplanned needs (e.g. a few people bathing in a very short time) and is used to transfer high temperature water from the main tank to the buffer tank. This transfer of water increases the efficiency of solar collector installations.

2 Consumption of hot water in a single-family building

The consumption of hot water in a building can be estimated theoretically on the basis of various legal regulations [2–6] or measured, obtaining its actual consumption. The estimated amount of water consumed may depend on the number of users, the type of building, metering with water meters [2, 4−6] or relative to the area of a heated flat or building [3]. The monthly demand for hot water related to the number of residents is calculated according to the formula:

𝐺𝐺�= 𝑞𝑞�∙ 𝐿𝐿�· 𝐿𝐿����� ��

������ (1)

where:

qi – unitary daily demand for hot water, dm3/(person·day) [2,4]; Li – number of users, people;

Lk – number of days in a month, days.

The monthly demand for hot water related to the area of the heated building is calculated according to the formula:

𝐺𝐺�= 𝑉𝑉�∙ 𝐴𝐴�· 𝐿𝐿�������

���������� (2)

where:

VW – unitary daily demand for hot water; dm3/(m2·day) [3]; Af – heated area of the building, m2.

(3)

single-hot water installation, that is its production, storage (storage tank insulation class), distribution (type of insulation of distribution and circulating pipes, circulation work time per day) and use (% age consumption of the prepared hot water volume). Ultimately, knowledge of the usable energy and efficiency of the installation allows us to determine the final energy.

In contrast, devices that produce energy to heat hot tap water can be supplied with various fuels, such as electricity, natural or liquid gas, coal, coke, wood, fuel oil, geothermal energy, biofuel or solar. Thermal energy obtained from the said fuels is burdened with a certain production cost. Expenses borne by the residents related to the consumption of heat and power are generated by the aforementioned factors. Each user is interested in incurring the lowest possible costs, and periodically even zero. This goal can be realized for many months of the year, using a hot tap water heating installation with solar collectors. The following chapters present the actual consumption of hot tap water in a single-family house in a period of 7 years, the amount of thermal energy acquired by solar collectors as well as monthly and annual coverage of usable and final energy generated by the solar collectors.

In the single-family building in Warsaw under consideration, hot water was prepared centrally and accumulated in a bivalent tank with a capacity of 300 litres. The tank has an additional heater and two coils, where the lower one is supplied from the solar system and the upper one (if necessary) from a central heating boiler. The solar installation consists of two collectors with a total active absorber area of 4.70 m2. The collectors are directed to the south and set at an angle of 55º to the level [1]. In 2013, the hot water installation was modernized by installing an additional 70-litre tank. This acts as a buffer tank performing two functions. First of all, it stores some of the hot water with a higher temperature for so-called unplanned needs (e.g. a few people bathing in a very short time) and is used to transfer high temperature water from the main tank to the buffer tank. This transfer of water increases the efficiency of solar collector installations.

2 Consumption of hot water in a single-family building

The consumption of hot water in a building can be estimated theoretically on the basis of various legal regulations [2–6] or measured, obtaining its actual consumption. The estimated amount of water consumed may depend on the number of users, the type of building, metering with water meters [2, 4−6] or relative to the area of a heated flat or building [3]. The monthly demand for hot water related to the number of residents is calculated according to the formula:

𝐺𝐺�= 𝑞𝑞�∙ 𝐿𝐿�· 𝐿𝐿�������

������ (1)

where:

qi – unitary daily demand for hot water, dm3/(person·day) [2,4]; Li – number of users, people;

Lk – number of days in a month, days.

The monthly demand for hot water related to the area of the heated building is calculated according to the formula:

𝐺𝐺�= 𝑉𝑉�∙ 𝐴𝐴�· 𝐿𝐿�������

���������� (2)

where:

VW – unitary daily demand for hot water; dm3/(m2·day) [3]; Af – heated area of the building, m2.

Actual monthly and annual consumption of hot water and estimated quantities according to different legal provisions are shown in Figures 1−2, 35 dm3/(person·day) for a

single-family house according to [2], 48 dm3/(person·day) for a residential building according to [2], 120 dm3/(person·day) for a residential building according to [4] and 1.4 dm3/(m2·day) for a single-family building according to [3]. The heated area of the analysed building Af = 109.89 m2.

Fig. 1. Annual consumption of hot water in a single-family house in m3.

Fig. 2. Monthly and average annual consumption of hot water in m3 in the years 2011–2017.

The number of residents living in the building in the years 2011–2017 changed from 3–5 people. However, the average annual number of inhabitants in this period varied from 3.02–3.81 people. The actual number of inhabitants in particular months is shown in Fig. 3. The fractional number of people in a given month means the proportional time of residence of a person in the building in relation to the length of a month.

30,0 40,0 50,0 60,0 70,0 80,0 90,0 100,0 110,0 120,0 130,0 140,0 150,0 160,0 170,0 2010 2011 2012 2013 2014 2015 2016 2017 2018

Factual by [2] by [1] 35 l/pers. by [1] 48 l/pers. by [3] 120 l/pers.

(4)

Fig. 3. Monthly and average annual number of inhabitants in 2011–2017.

3 Demand for usable and final energy for the needs of preparing

usable hot water

Calculations of the final energy demand for the needs of hot water preparation can be performed using algorithms from the "Methodology for calculating the energy performance of a building" [3]. The final energy demand is calculated from the formula:

[ ]

kWh Q Q tot W nd W W K , , , =η (3) e W s W d W g W tot W, η , η , η , η , η = ⋅ ⋅ ⋅ (4) where:

QW,nd – demand for useful heat for heating hot water; kWh/year;

ηW,tot – total annual average efficiency of the domestic hot water preparation system; ηW,g – average annual efficiency of heat generation from an energy carrier or energy supplied to a heat source (0.82 was assumed according to the data of the existing boiler);

ηW,d – average annual efficiency of heat transfer from a heat source to hot taps (0.95 for the existing installation);

ηW,s – average annual efficiency of heat accumulation in capacitive elements of the domestic hot water preparation system (0.85 is assumed for the existing storage tank);

ηW,g – average annual efficiency of heat utilization (1.0 assumed).

The demand for useful heat for heating hot water is calculated as follows:

(

)

    − ⋅ ⋅ ⋅ = month kWh c G Q W W W CW ZW nd W, ρ3600θ θ (5) where:

GW – actual or design consumption of hot water in the building in dm3/month;

(5)

Fig. 3. Monthly and average annual number of inhabitants in 2011–2017.

3 Demand for usable and final energy for the needs of preparing

usable hot water

Calculations of the final energy demand for the needs of hot water preparation can be performed using algorithms from the "Methodology for calculating the energy performance of a building" [3]. The final energy demand is calculated from the formula:

[ ]

kWh Q Q tot W nd W W K , , , =η (3) e W s W d W g W tot W, η , η , η , η , η = ⋅ ⋅ ⋅ (4) where:

QW,nd – demand for useful heat for heating hot water; kWh/year;

ηW,tot – total annual average efficiency of the domestic hot water preparation system; ηW,g – average annual efficiency of heat generation from an energy carrier or energy supplied to a heat source (0.82 was assumed according to the data of the existing boiler);

ηW,d – average annual efficiency of heat transfer from a heat source to hot taps (0.95 for the existing installation);

ηW,s – average annual efficiency of heat accumulation in capacitive elements of the domestic hot water preparation system (0.85 is assumed for the existing storage tank);

ηW,g – average annual efficiency of heat utilization (1.0 assumed).

The demand for useful heat for heating hot water is calculated as follows:

(

)

    − ⋅ ⋅ ⋅ = month kWh c G Q W W W CW ZW nd W, ρ3600θ θ (5) where:

GW – actual or design consumption of hot water in the building in dm3/month;

2,8 3 3,2 3,4 3,6 3,8 4 4,2 4,4 4,6 4,8 5 2011 2012 2013 2014 2015 2016 2017

cW – specific heat of water, assumed as 4.19 kJ/(kg·K); ρW – density of water, assumed as 1.0 kg/dm3;

θCW – temperature of hot water in the inlet valve (assumed as 40°C);

θZW – cold water temperature, based on measurements or assumed as an annual average of 10°C. The coverage of usable energy from the solar collector installation is calculated as follows:

[ ]

% % 100 , , , = ⋅ nd W kol K nd W Q Q P (6)

The coverage of final energy from the solar collector installation is calculated as follows:

[ ]

% % 100 , , , = ⋅ W K kol K W K QQ P (7) where:

QK,kol – final energy obtained by the solar collector installation in kWh.

Table 1 presents the results of the study of one selected year from the period 2011–2017, i.e.: consumption of hot water in a single-family house, demand for usable and final energy, the amount of energy obtained from the solar collector installation, the amount of final energy covered by the heat source and coverage percentages of usable and final energy through the solar installation. For the calculation of usable and final energy an average daily temperature of hot water in the intake valve equal to 40°C was assumed.

Table 1. Usable and final energy for the preparation of hot water and their coverage in 2016.

Month Consumption of hot tap water Gw Temperature of cold water θZW Usable energy QW,nd Final energy QK,W Final energy from solar collectors QK,kol Final energy from heat source Coverage of QW,nd by collectors Coverage of QK,W by collectors [m3] [°C] [kWh] [kWh] [kWh] [kWh] [%] [%] 1 2 3 4 5 6 7 8 9 January 3.57 6 141.3 213.4 43.5 169.9 30.8 20.4 February 5.27 7 202.4 305.7 64.5 241.2 31.9 21.1 March 4.80 8 178.8 270.0 69.0 201.0 38.6 25.6 April 3.88 9 140.0 211.4 100.5 110.9 71.8 47.5 May 4.60 10 160.6 242.6 142.5 100.1 88.7 58.7 June 4.30 13 135.1 204.1 162.0 42.1 119.9 79.4 July 4.20 14 127.1 191.9 160.5 31.4 126.3 83.6 August 4.48 15 130.4 196.9 169.5 27.4 130.0 86.1 September 4.39 13 138.0 208.3 157.5 50.8 114.2 75.6 October 4.54 10 158.5 239.4 40.5 198.9 25.5 16.9 November 4.41 8 164.2 248.1 40.5 207.6 24.7 16.3 December 4.48 7 172.1 259.9 30.0 229.9 17.4 11.5 average 4.40 10 154.0 232.6 98.4 134.3 63.9 42.3 total 52.92 - 1848.4 2791.6 1180.5 1611.1 - -

(6)

However, Table 2 presents the average annual values of hot water consumption, the types of energy and their coverage by the solar collector installation for a period of seven years (2011–2017). Monthly coverage of usable and final energy in 2016 is shown in Fig. 4. A very high degree of coverage of usable and final energy can be observed by the solar collector installation in the four summer months (June–September) and the lowest annual coverage in the autumn months (October–December). This was a result of a very hot and sunny summer period and a cloudy autumn in 2016.

Table 2. The average annual consumption of types of energy for hot water preparation and their coverage in the period 2011–2017.

Year Consumption of hot tap water Gw Temperature of cold water θZW Usable energy QW,nd Final energy QK,W Final energy from solar collectors QK,kol Final energy from heat source Coverage of QW,nd by collectors Coverage of QK,W by collectors [m3] [°C] [kWh] [kWh] [kWh] [kWh] [%] [%] 1 2 3 4 5 6 7 8 9 2011 86.3 10 2992 4518 1756 2762 59 39 2012 82.9 10 2876 4344 1536 2808 53 35 2013 81.6 10 2858 4317 1136 3181 40 26 2014 77.8 10 2715 4100 1033 3067 38 25 2015 61.4 10 2152 3249 1045 2204 49 32 2016 52.9 10 1848 2792 1181 1611 64 42 2017 52.4 10 1830 2763 1071 1692 59 39 averag e 70.8 10 2467 3726 1251 2475 51 34

Fig. 4. Monthly energy coverage by solar collectors for the preparation of hot water in 2016.

0% 20% 40% 60% 80% 100% 120% 140%

(7)

However, Table 2 presents the average annual values of hot water consumption, the types of energy and their coverage by the solar collector installation for a period of seven years (2011–2017). Monthly coverage of usable and final energy in 2016 is shown in Fig. 4. A very high degree of coverage of usable and final energy can be observed by the solar collector installation in the four summer months (June–September) and the lowest annual coverage in the autumn months (October–December). This was a result of a very hot and sunny summer period and a cloudy autumn in 2016.

Table 2. The average annual consumption of types of energy for hot water preparation and their coverage in the period 2011–2017.

Year Consumption of hot tap water Gw Temperature of cold water θZW Usable energy QW,nd Final energy QK,W Final energy from solar collectors QK,kol Final energy from heat source Coverage of QW,nd by collectors Coverage of QK,W by collectors [m3] [°C] [kWh] [kWh] [kWh] [kWh] [%] [%] 1 2 3 4 5 6 7 8 9 2011 86.3 10 2992 4518 1756 2762 59 39 2012 82.9 10 2876 4344 1536 2808 53 35 2013 81.6 10 2858 4317 1136 3181 40 26 2014 77.8 10 2715 4100 1033 3067 38 25 2015 61.4 10 2152 3249 1045 2204 49 32 2016 52.9 10 1848 2792 1181 1611 64 42 2017 52.4 10 1830 2763 1071 1692 59 39 averag e 70.8 10 2467 3726 1251 2475 51 34

Fig. 4. Monthly energy coverage by solar collectors for the preparation of hot water in 2016.

0% 20% 40% 60% 80% 100% 120% 140%

Usable energy Qw,nd Final energy Qk,w

The average annual consumption of usable and final energy and the energy obtained from solar collectors for hot water preparation in the period 2011–2017 are shown in Fig. 5. There was a downward trend in consumption of final and usable energy in subsequent years, which is a clear effect of declining consumption of hot water in the building during this period. The decreasing consumption of hot water in the building results directly from the number of inhabitants but also from the installation of energy-saving household appliances in 2015 [7].

Fig. 5. Annual energy consumption in kWh for hot water preparation in the period 2011–2017.

Fig. 6. Annual energy coverage for water heated by solar collectors in the period 2011–2017. 750 1250 1750 2250 2750 3250 3750 4250 4750 2010 2011 2012 2013 2014 2015 2016 2017 2018

Usable energy Qw,nd Final energy Qk,w solar collectors QK,kol

20% 25% 30% 35% 40% 45% 50% 55% 60% 65% 70% 2010 2011 2012 2013 2014 2015 2016 2017 2018

(8)

4 Summary

The presented research results should be treated as a case study. They refer to one specific building, inhabited by a specific number of people and equipped with a non-standard hot water installation. Based on the results of the research, it can be concluded that the highest energy coverage for the preparation of hot water by solar collectors occurs in the summer months, i.e. from June to September. The usable energy in the summer months was covered from 37%–142% and the final energy from 25%–94% respectively. The average annual coverage of these energies in the period of 7 years was respectively: 51% of usable energy (min. 38%, max. 64%), final energy 34% (min. 25%, max. 42%). The highest energy coverage occurred in the last two years (2016 and 2017) in which the lowest consumption of hot water per person was recorded, respectively 48.01 and 47.58 [dm3/(person·day)]. In the analysed building, the energy coverage for heating hot water depends to a large extent on the amount of its consumption. To increase the degree of energy coverage in this building, it would be necessary to increase the surface area of solar collectors or to use a different type of collectors with higher efficiency. It is true that the area of collectors related to one inhabitant (1.56 m2/person) is within the range of design recommendations (1–2 m2/person); however, this does not provide full energy coverage. Therefore, when designing solar collectors, one should also pay attention to the amount of hot water used, which will not be a simple task for most single-family houses. The operational experience shows that the building users, despite the incomplete coverage of energy needs by the solar collectors and the occasional one-day shortage of hot water, are satisfied with the benefits of this solar installation.

References

1. A. Starakiewicz, ZN PRz. 57, 509−514 (2010)

2. Rozp. Min. Infr. z dnia 6 listopada 2008 r. w sprawie metodologii obliczania charakterystyki energetycznej budynku i lokalu mieszkalnego lub części budynku stanowiącej samodzielna całość techniczno-użytkowa oraz sposobu sporządzania i wzorów świadectw ich charakterystyki energetycznej. (Dz. U. z 2008 r. Nr 201, poz.1240)

3. Rozp. Min. Infr. i Roz. z dnia 27 lutego 2015 r. w sprawie metodologii wyznaczania charakterystyki energetycznej budynku lub części budynku oraz świadectw charakterystyki energetycznej (Dz. U. z 18 marca 2015 r., poz. 376)

4. PN-92/B-01706, Instalacje wodociągowe. Wymagania w projektowaniu – wraz ze zmianą (PN-B-01706:1992/Az1:1999)

5. Rozp. Min. Spr. Wewn. i Adm. z dnia 31 maja 2000 r. zmieniające rozporządzenie w sprawie wprowadzenia obowiązku stosowania niektórych Polskich Norm. (Dz. U. z 2000 r. Nr 51, poz. 617)

6. Rozporządzenie Ministra Infrastruktury z dnia 14 stycznia 2002 r. W sprawie określenia przeciętnych norm zużycia wody. (Dz. U. Z 2002 r. Nr 8, poz. 70)

Riferimenti

Documenti correlati

A comparative analysis regarding water consumption in various time periods was conducted on the basis of measurements related to two identical buildings as far as their

(1) as the difference between the useful heat energy supplied to the tap water system in the hotel E DHW and electrical energy consumed by the pumps EP divided by solar

(MWA Annual Report 2016) During the flooding crisis of Bangkok, although, MWA tap water had confidently complied with WHO guidelines level 2011 (Kitkaew, et.al, 2013), customers

The blaTEM-1, tetA, tetG, sulI, ermA and ermB genes were present in every sample, while ampC was found only in disinfected and tap water samples, indicating the promotion

The analyses of the energy consumption used for the purposes of DHW preparation, presented in the further part of the article, have been based on an actual hot water

The economic analysis shows that in the assumed life cycle (20 years), the total cost for a heating system based on a gas boiler is lower than in the case of a heat pump by

The examined objects were treated as typical examples of single-family buildings. The airtightness test relates to the building envelope, so the impact of the ventilation system used

The genera and species detected in this study belong mainly to the typical, environmental strains, often found in tap water samples. albertii) are associated with human infections