Functioning limits

Cooling cycle:

B.S. air side exchanger intake air temperature:

20°C ÷ 42°C with output water temperature at 7°C.

In no case should the unit operate normally with output water temperature above 18°C.

T (°C)=Outdoor air temperature B.S.

t (°C)=Water temperature

Temperature differential on the evaporator: t = 3÷8°C.

Functioning with condensing control (KFI) Standard functioning

 Minimun water pressure = 0,5bar

 Maximum water pressure = 3bar Heating cycle (for THCEY)

B.U. air side exchanger intake air temperature: -5°C ÷ 20°C.

Outputwater temperature: 30°C÷55°C.

0 5

-5 10 15 20 40

40 35 45

KFI 50

53

-10

114÷128

T (°C)=Outdoor air temperature B.U.

t (°C)=Water temperature

Maximum water inlet temperature 48°C

Temperature gradient on the condenser ∆T = 3 ÷ 8°C.

Functioning with condensing control (KFI) Standard functioning

 Minimun water pressure = 0,5bar

 Maximum water pressure = 3bar

SECTION I : USER

I.6 WARNINGS REGARDING POTENTIALLY TOXIC

SUBSTANCES

DANGER!

Read the following information about the refrigerants employed carefully.

I.6.1.1 Identification of the type of refrigerant fluid used

 Difluorometano (HFC 32) 50% in weight N° CAS: 000075-10-5

 Pentafluoroetano (HFC 125) 50% in weight N° CAS: 000354-33-6

I.6.1.2 Identification of the type of oil used

The lubricant used in the unit is polyester oil; please refer to the indications on the compressor data plate.

DANGER!

For further information regarding the

characteristics of the refrigerant and oil used, refer to the safety data sheets available from the refrigerant and oil manufacturers.

I.6.1.3 Main ecological information regarding the types of refrigerant fluids used

 Persistence, degradation and environmental impact.

Fluid Chemical formula GWP (over 100 years)

R32 CH2F2 550

R125 C2HF5 3400

HFC R32 and R125 refrigerants are the single components which mixed at 50% make up R410A. They belong to the hydrofluorocarbons group and are regulated by the Kyoto protocol (1997 and subsequent revisions) being gases that contribute to the greenhouse effect. The index which measures how much a certain mass of greenhouse gas contributes to global warming is the GWP (Global Warming Potential).

The standard measure for carbon dioxide (CO2) is GWP=1.

The value of GWP assigned to each refrigerant represents the equivalent amount in kg of CO2 released over a period of 100 years, in order to have the same greenhouse effect of 1kg refrigerant released over the same period of time.

The R410A mixture does not contain elements that are harmful to the ozone layer, such as chlorine;, therefore, its ODP (Ozone Depletion Potential) is zero (ODP=0).

Refrigerant R410A Components R32/R125 Composition 50/50

ODP 0 GWP (over 100 years) 2000 SAFEGUARD THE ENVIRONMENT!

The hydrofluorocarbons contained in the unit cannot be released into the atmosphere as they are gases that contribute to the greenhouse effect.

R32 and R125 are hydrocarbons which decompose rapidly into the lower atmosphere (troposphere). Decomposition by-products are highly dispersible and thus have a very low concentration. They do not affect photochemical smog (that is, they are not classified among VOC volatile organic compounds, according to the guidelines established by the UNECE agreement).

 Effects on effluent treatment

Waste products released into the atmosphere do not cause long-term water contamination.

 Personal protection/exposure control

Use protective clothing and gloves; protect eyes and face.

 Professional exposure limits:

R410A

HFC 32 TWA 1000 ppm

HFC 125 TWA 1000 ppm

 Handling

DANGER!

Users and maintenance personnel must be adequately informed about the risks of handling potentially toxic substances. Failure to observe the aforesaid indications may cause personal injury or damage the unit.

Avoid inhalation of high concentrations of vapour. The atmospheric concentration must be reduced as far as possible and maintained at this minimum level, below professional exposure limits. The vapours are heavier than air, and thus hazardous concentrations may form close to the floor, where overall ventilation may be poor. In this case, ensure adequate ventilation. Avoid contact with naked flames and hot surfaces, which could lead to the formation of irritant and toxic decomposition by-products. Do not allow the liquid to come into contact with eyes or skin.

 Procedures in case of accidental refrigerant leakage Ensure adequate personal protection (using means of respiratory protection) during clean-up operations. If the conditions are sufficiently safe, isolate the source of leak.

If the extent of the spill is limited, let the material evaporate, as long as adequate ventilation can be ensured. If the spill is considerable, ventilate the area adequately.

Contain the spilt material with sand, soil, or other suitable absorbent material.

Prevent the liquid from entering drains, sewers, underground facilities or manholes, because suffocating vapours may form.

I.6.1.4 Main toxicological information on the type of refrigerant used

 Inhalation

A high atmospheric concentration can cause anaesthetic effects with possible loss of consciousness. Prolonged exposure may lead to an irregular heartbeat and cause sudden death.

Higher concentrations may cause asphyxia due to the reduced oxygen content in the atmosphere.

 Contact with skin

Splashes of nebulised liquid can produce frostbite. Probably not hazardous if absorbed through the skin. Repeated or prolonged contact may remove the skin's natural oils, with consequent dryness, cracking and dermatitis.

 Contact with eyes

Splashes of liquid may cause frostbite.

 Ingestion

While highly improbable, may produce frostbite.

I.6.1.5 First aid measures

 Inhalation

Move the person away from the source of exposure, keep him/her warm and let him/her rest. Administer oxygen if necessary. Attempt artificial respiration if breathing has stopped or shows signs of stopping.

In the case of cardiac arrest carry out heart massage and seek immediate medical assistance.

 Contact with skin

In case of contact with skin, wash immediately with lukewarm water.

Thaw tissue using water. Remove contaminated clothing. Clothing may stick to the skin in case of frostbite. If irritation, swelling or blisters appear, seek medical assistance.

 Contact with eyes

Rinse immediately using an eyewash or clean water, keeping eyelids open, for at least ten minutes.

Seek medical assistance.

 Ingestion

Do not induce vomiting. If the injured person is conscious, rinse his/her mouth with water and make him/her drink 200-300 ml of water.

Seek immediate medical assistance.

 Further medical treatment

Treat symptoms and carry out support therapy as indicated. Do not administer adrenaline or similar sympathomimetic drugs following exposure, due to the risk of cardiac arrhythmia.

SECTION I : USER

I.6.2 INFORMATION ABOUT RESIDUAL RISKS

THAT CANNOT BE ELIMINATED

Fig. 2

Indicates the presence of moving parts 
 (belts, fans)

Indicates the presence of hot surfaces
 (cooling circuit, compressor heads)

Indicates the presence of live components

Indicates the presence of sharp edges on finned coils

I.7 DESCRIPTION OF CONTROLS

The controls consist of the master switch, circuit breakerand user interface panel.

I.7.1 GENERAL SWITCH

Manually controlled type "b" mains power supply disconnection device (ref. EN 60204-1§5.3.2).

I.7.2 CIRCUIT BREAKER SWITCHES

 Automatic compressor protection switch

This switch allows supplying or isolating the compressor's power circuit.

 Fan protection fuses (for sizes 114-126) Fuses for fan protection and fan power circuit isolation

 Fan protection circuit breaker switch (for size 128) The switch supplies power and isolates the fan power circuit.

SECTION II : INSTALLATION AND MAINTENANCE

II SECTION II :: INSTALLATION AND MAINTENANCE

II.1 DESCRIPTION OF THE UNIT II.1.1 STRUCTURAL FEATURES

○ Chassis made of Peraluman panels; base in galvanised sheet steel;

sound proofed compressor chamber.

○ 1 Scroll rotary hermetic compressor complete with externalcircuit breaker protection.

○ Water side plate brazed plate exchanger in stainless steel complete with antifreeze resistance, expanded polyurethane insulation and air bleed valve inside the machine.

○ Air side exchanger composed of coil with copper pipes and aluminium fins, complete with protection grille.

○ Directly coupled centrifugal electric fan equipped with internal circuit breaker protection, vertical condensation and evaporation air flow and complete with protection networks.

○ Male threaded hydraulic fittings.

○ Differential pressure switch that protect the unit from any water flow interruptions.

○ Cooling circuit realised with annealed copper pipes (EN 12735-1-2) complete with: drier filter, load connections, high pressure side manual rearming safety pressure switch, safety valve, automatic rearming pressure switch to control low side pressure, liquid-moisture indicator, thermostatic expansion valve (2 for THCEY), cycle inversion valve (for THCEY), safety valve liquid receiver (for THCEY) and check valve (2 for THCEY).

○ The T version is complete with storage, expansion vessel calculated for the quantity of water present inside the machine (maximum operating pressure 3 bar, pre-load 1 bar, 7l capacity), 3 bar safety valve, drain cocks (supplied and to be installed), manual bleed valve, pump (121 T-128 T), circulator (114 T-117 T) or high head pump (114 H-117 H).

○ Unit complete with:

 Condensation drain tray (for THCEY);

 compatible with AdaptiveFunction Plus function.

 Ecological R410A refrigerant fluid load.

II.1.2 ELECTRICAL CONTROL BOARD

○ Electrical panel accessed by removing the upper left panel,

compliant with IEC Standards in force, which can be opened and closed with a suitable tool.

○ Complete with:

 electrical wiring arranged for power supply 400V-3ph+N-50Hz;

 auxiliary circuit power supply 230V-1ph-50Hz derived from main power supply;

 main power supply switch with interlocking safety door isolator;

 automatic compressor protection switch;

 auxiliary circuit protection fuse;

 Fan protection fuse (114-126);

 Automatic switch for fan protection (128)

 compressor power contactor;

 removable machine controls.

○ Programmable microprocessor electronic board handled by the keyboard inserted in the machine. This electronic board performs the following functions:

 Regulation and management of the set points for unit flow water temperature; cycle inversion (for THCEY); safety timer delays;

circulating pump; compressor and pump hour-run meter; temperature defrost cycles (for THCEY); electronic anti-freeze protection which cuts in automatically when the machine is switched off; and functions which control the operation of the individual parts making up the machine;

 complete protection of the unit, possible shutdown and display of all the triggered alarms;

 compressor protection phase sequence monitor;

 unit protection against low or high phase power supply voltage;

 visualisation of the programmed sets via display; of the in/out water temperatures via display; of the alarms via display; of chiller or heat pump operation via LED (for THCEY); of the electrical tension values present in the three phases of the electrical power circuit supplying the unit;

 self-diagnosis with continuous monitoring of the unit functioning status.

 user interface menu;

 alarms log management (if the KTR accessory is present, menu protected by factory password). In particular, for every alarm, the following are memorised:

 date and time of intervention (if the KSC accessory is present);

 alarm code and description;

 inlet/outlet water temperatures values when the alarm intervened;

 the condensation pressure values at the time of the alarm (if the KFI accessory is present);

 alarm delay time from the switch-on of the connected device;

 compressor and fan status at the time of the alarm (if the KFI accessory is present, it displays the output status in analogue);

○ Advanced functions:

 set-up for serial connection (KRS485, KFTT10, KRS232, KUSB accessory);

 configured to manage time slots and work parameters with the possibility of daily/weekly operation planning;

 check-up and monitoring of scheduled maintenance status;

 computer-assisted unit testing;

 self-diagnosis with continuous monitoring of the unit functioning status.

 dynamic set-point adjustment (AdaptiveFunctionPlusfunction).

II.2 SPARE PARTS AND ACCESSORIES

IMPORTANT!

Only Use original spare parts and accessories.

RHOSS S.p.A. shall not be held liable for damage caused by tampering with or work carried out by unauthorised personnel or malfunctions caused by the use of non-original spare parts or accessories.

II.2.1 FACTORY FITTED ACCESSORIES

RAA – Storage antifreeze resistance..

USC – Horizontal fan expulsion air flow.

SIL – compressor soundproofing via muffler.

DSP – Double set-point via digital consensus (incompatible with the CS accessory). It is only compatible with Precision mode.

CS – sliding set point via 4-20mA analogue (incompatible with DSP and KEAP accessories). It is only compatible with Precision mode.

SFS – Soft Starter device

RCC – compressor crankcase heater.

II.2.2 ACCESSORIES SUPPLIED SEPARATELY

KFA – Water filter.

KSA – Rubber anti-vibration mountings

KVDEV – 3-way diverter valve for managing the production of domestic hot water.

KRIT –Supplementary electric heater for heat pump.

KFI – Low ambient control for continuous control of the fan rotation speed down to outdoor air temperatures of –10°C during chiller operation, for ambient air temperatures up to 30°C during heat pump.

KTR – Keyboard for remote control with backlit LCD display.

KSC - Clock card to display date/time and to regulate the machine with daily/weekly start/stop time bands, with the possibility to change the set-points. The settings can be set from the remote keyboard (KTR) or by the supervisor.

SECTION II : INSTALLATION AND MAINTENANCE KRS485 – Logic dialogue serial RS485 interface with building

automation and supervisory systems (Supported protocols: owner protocol; RTU Modbus®).

KFTT10 – Serial FTT10 interface to connect to LonWorks® compatible protocol supervisory systems.

KRS232 – RS485/RS232 serial converter to connect to supervisory systems and must be associated to one or more KRS485 serial interface modules in the case of centralised unit management.

KUSB – RS485/USB serial converter to connect to supervisory systems and must be associated to one or more KRS485 serial interface modules in the case of serial unit management.

KRAS – Intake anti-vibrating fitting KRMA – Flow anti-vibrating fitting

Description and fitting instructions are supplied with each accessory.

II.3 TRANSPORT - HANDLING AND STORAGE

DANGER!

The unit must be transported and handled by skilled personnel trained to carry out this type of work.

SAFEGUARD THE ENVIRONMENT!

Dispose of the packaging materials in compliance with the national or local legislation in force in your country. Do not leave the packaging within reach of children.

IMPORTANT!

Be careful to prevent damage by accidental collision.

II.3.1 PACKAGING COMPONENTS

DANGER!

Do not open or tamper with the packaging before installation.

The units must only be moved and lifted by specialised personnel who are trained to do so.

Bring the machine to the installation site with packaging intact using a forklift truck or hand truck, making sure it is not off centre (position of symbol approximate, always check stability).

The units are supplied inside a cardboard box on top of a wooden pallet secured with 4 screws and strapped.

Each unit is supplied complete with:

 User instructions

 wiring diagram

 list of authorised service centres

 warranty document

 safety valve certificates

 safety valve, fan and pump or circulator use and maintenance manuals.

II.4 HANDLING GUIDELINES

DANGER!

An off-centred barycentre could cause sudden and hazardous movements. Movement of the unit must be performed with care, in order to avoid damage to the external structure and to the internal

mechanical and electrical components.

Also make sure that there are no obstacles or people along the route, in order to prevent the risk of impact, crushing or tipping the lifting device.

TCCE – THCE 114÷128

X Y

Y X

G G

G G

TCCE – THCE 114÷128T-H

Fig.5 Approximate centre of gravity position.

X Y Weight (*)

MODEL

(cm) (cm) kg

TCCEY 114 56,5 28,0 260

TCCEY 117 55,0 26,5 280

TCCEY 121 65,0 31,2 350

TCCEY 126 65,0 31,0 370

TCCEY 128 65,0 31,0 370

THCEY 114 56,5 28,0 280

THCEY 117 55,0 26,5 290

THCEY 121 65,0 34,2 370

THCEY 126 65,0 34,0 380

THCEY 128 65,0 34,0 380

TCCEY 114 T-H 62,0 25,6 350

TCCEY 117 T-H 61,0 27,1 370

TCCEY 121 T 73,5 32,0 440

TCCEY 126 T 73,0 32,2 470

TCCEY 128 T 73,0 32,2 470

THCEY 114 T-H 57,0 27,1 360

THCEY 117 T-H 62,0 26,6 380

THCEY 121 T 73,0 34,0 450

THCEY 126 T 72,5 34,2 480

SECTION II : INSTALLATION AND MAINTENANCE The machine must only be lifted up unpacked to remove the pallet

and/or to set it on the ground. First remove the 4 fixing screws. All handling operations must be carried out with the utmost attention and care. Do not use this method for lifting or movement operations other than those described.

To lift the unpacked unit, use non-worn fabric belts with guards for sharp corners. Harness the machine as shown in Fig. 6, passing the fabric belts through the specific slots on the base. Tension the belts, checking that they remain properly attached to the upper edge of the slot; lift the unit a few centimetres, then, only after checking the stability of the load, slide the pallet out, taking care not to trap any body parts, in order to eliminate any possible risk of crushing or any other injury if the load drops or shifts suddenly. Lower the machine slowly and secure it to the ground.

Remove the protective film from the panels once the machine has been installed.

SAFEGUARD THE ENVIRONMENT!

Dispose of the packaging materials in compliance with the national or local legislation in force in your country.

DANGER!

Do not leave the packaging within reach of children.

II.4.1 STORAGE CONDITIONS

The units cannot be stacked. The temperature limits for storage are -20÷60°C.

II.5 INSTALLATION INSTRUCTIONS

DANGER!

Installation must only be carried out by skilled technicians, qualified for working on air

conditioning and refrigeration systems. Incorrect installation could cause the unit to run badly, with a consequent deterioration in performance.

DANGER!

The unit must be installed according to national or local standards in force at the time of installation.

Use protective grilles or other devices to prevent possible contact should the unit be accessible to persons younger than 14 years of age. The documentation for accessories supplied loose included with each kit.

DANGER!

Do not lean on the thermal exchange coil or corners of the structure as improper use could cause cuts;

use appropriate personal protective equipment (gloves, goggles, etc.).

DANGER!

When the outdoor temperature is around zero, the water normally produced during the coil defrosting could form ice and make the flooring near the unit

If the unit is not fixed to anti-vibration mounts (KSA), once it has been set on the ground, it must be firmly bolted down to the floor using M10 metric threaded bolts. Slots are provided in the base for this purpose.

II.5.1 INSTALLATION SITE REQUIREMENTS

The installation site should be chosen in accordance with the provisions of Standard EN 378-1 and in keeping with the requirements of Standard EN 378-3. When selecting the installation site, risks posed by accidental refrigerant leakage from the unit should also be taken into

consideration.

II.5.2 INDOOR INSTALLATION

Machines designed forindoor installation must be positioned so as to prevent any refrigerant gas leakages from spreading inside the building and posing a hazard to people's health.

If the unit is installed on terraces or building roofs, adequate safety measures must be taken in order to ensure that any gas leaks cannot enter the building through ventilation systems, doors or similar openings.

In the event that the unit is installed inside a walled-in structure (usually for aesthetic reasons), these structures must be suitably ventilated in order to prevent the formation of dangerous concentrations of refrigerant gas.

II.5.3 SPACE, POSITIONING AND CHANNELLING

The unit is envisioned for indoorinstallation. The unit must be installed in compliance with the minimum recommended technical spaces, bearing in mind the access to the water and electrical connections. The unit should be correctly levelled and positioned on a supporting surface capable of sustaining its full weight. It must not be installed on brackets or shelves.

To allow the TCCEY and THCEY units to run smoothly it is

recommended not to mix the drawn air with the expelled air, therefore it is advisable to channel and expel out of the room where the unit is installed.

Flow channelling must always have constant section equal to the fan flow section. To prevent vibration transmission, the KRAM kit is available (outlet anti-vibration fitting) which allows the unit to be separated from the duct. It is therefore advisable to apply elastic fittings on the air duct in the points where it passes through the walls of the room.

The room in which the unit is to be installed must have an opening that allows the air to be drawn from the outside through a section that is at least equal to the surface of the finned coil.

The intake can be channelled. The KRAS kit (inlet anti-vibration fitting) is available to prevent vibration transmission.

SECTION II : INSTALLATION AND MAINTENANCE

SECTION II : INSTALLATION AND MAINTENANCE