4 ASSEGNAZIONE DEL GUASTO INTERNO 999
5 OPERATING CONTROL AND DISPLAYS
5.5 MANUAL MENU PATH
5.6.1 ENTER PASSWORD
Display menu "password settings"
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the "password setting" menu.
Fig. 5-24 Enter password menu 1 Password pictogram (selected) 2 Enter password
3 Access level 2 displayed with access au-thorisation
• Use the cursor keys to select the password field you wish to change.
• Change the number with the cursor keys .
• Confirm the password with Enter .
Configure program sequence
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the program sequence overview.
Fig. 5-25 Overview program sequence 1 Duration of pre-ventilation [selected]
2 Pilot burner oil operation 3 Duration of post-ventilation 4 Valve leakage test 5 Pilot burner gas operation Set duration of pre-ventilation
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the "duration of pre-ventilation" menu.
1 2 3
Fig. 5-26 Duration of pre-ventilation menu 1 Duration of pre-ventilation pictogram 2 Pre-ventilation time set
3 Accept value by pressing ENTER
• Use the cursor keys to select the number you wish to change.
• Change the value of the number with the cursor keys .
• Confirm the entry with Enter . The countdown starts.
ENGLISH
Fig. 5-27 Secure data transfer 1 UI300 pictogram 2 BT300 pictogram 3 Cancel (back)
4 Parameter number UI300 5 Parameter number UI300
6 Transfer by pressing ENTER (flashing) 7 Value for UI300
8 Value for BT300
i
Do not accept the value until the values for UI300 and BT300 are the same! The value for the parameter has to be confirmed by pressing ENTER in the space of the count-down (8 s)!• Accept or discard the entry
i
The following sequence of events for confirming or discarding the entry is exactly the same for all parameter entries.Therefore this process is no longer illustrated in detail in the following explanations for the parameter settings.
You will simply find this text: "Accept or discard the entry!"
a) Confirm the entry in time by pressing Enter . The value is accepted.The display shows the following page:
Fig. 5-28 Display after successfully transferred data 1 Pictogram UI300
2 Pictogram BT300 3 Parameter number UI300 4 Parameter number BT300
!
If both values are equivalent, the value can be accepted by pressing ENTER. If there is a dis-crepancy with the values, terminate the "acceptance" process.b) Reject the change made to the parameter Select the Back key .The change made to the parameter is not accepted.The following page appears:
Fig. 5-29 Display of invalid data transfer 1 Pictogram UI300
2 Pictogram BT300 3 Parameter number UI300 4 Parameter number BT300 5 Pictogram apply parameters 6 Value BT300
7 Value UI300
Set duration of post-ventilation
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the "Duration of post-ventilation" menu.
1 Duration of post-ventilation pictogram 2 Set duration of post-ventilation 3 Accept setting by pressing ENTER
• Use the cursor keys to select the number you wish to change.
• Change the value of the number with the cursor keys .
ENGLISH
confirm this with Enter .
The display shows the valve leakage test menu.
Fig. 5-30 Submenü "Dichheitskontrolle"
1 Leakage test ON/OFF 2 Leakage test before ignition 3 Leakage test after ignition 4 Duration of leakage test
i
Access level 2 is required to set this function!Accept or discard the entry!
Activate valve leakage test prior to ignition
• Use the cursor keys to select the menu and confirm this with Enter .
• Change the ON/OFF functional state using the cursor keys and confirm this by pressing Enter .
The display shows the valve leakage test prior to ignition menu.
Fig. 5-31 Valve leakage test prior to ignition menu 1 Valve leakage test prior to ignition picto-gram 2 Display valve leakage test (active)
3 Accept setting by pressing Enter The valve leakage test is set!
i
Access level 2 is required to set this function!Accept or discard the entry!
Check valve leakage test after flame OFF
• Use the cursor keys to select the menu and confirm this with Enter .
• Change the ON/OFF functional state using the cursor keys
The display shows the valve leakage test after flame OFF menu.
Fig. 5-32 Valve leakage test after flame OFF menu 1 Valve leakage test after flame OFF picto-gram 2 Display valve leakage test
3 Accept setting by pressing Enter The valve leakage test is set!
i
Access level 2 is required to set this function!!Accept or discard the entry!
Set duration of valve leakage test
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the "duration of valve leakage test" menu.
Fig. 5-33 Valve leakage test menu.
1 Duration of valve leakage test pictogram 2 Set duration of valve leakage test 3 Accept setting by pressing Enter
• Use the cursor keys to select the number you wish to change.
• Change the value of the number with the cursor keys .
• Confirm the entry with Enter . Accept or discard the entry!
Activate the pilot burner in gas operation
• Use the cursor keys to select the menu and confirm this with Enter .
• Change the ON/OFF functional state using the cursor keys and confirm this bypressing Enter .
The display shows the "pilot burner in gas operation" menu
ENGLISH
Fig. 5-34 Pilot burner in gas operation menu 1 Pilot burner in gas operation pictogram 2 Activate the pilot burner in gas operation 3 Accept setting by pressing Enter.
i
Access level 2 is required to set this function!Accept or discard the entry!
Set pilot burner in oil operation
• Use the cursor keys to select the menu and confirm this with Enter .
• Change the ON/OFF functional state using the cursor keys and confirm this bypressing Enter .
The display shows the "pilot burner in oil operation" menu.
Fig. 5-35 Pilot burner in oil operation menu 1 Pilot burner in oil operation pictogram 2 Activate pilot burner in oil operation 3 Accept setting by pressing Enter
i
Access level 2 is required to set this function!Accept or discard the entry!
Configuration of actuating outputs
• Use the cursor keys to select the menu and confirm this with Enter .
The display shows the configuration of actuating outputs menu.
1 Actuating drive position pictogram 2 Display channel 1, oil
3 Display channel 2, air 4 Display channel 3, off 5 Optional channel, off
Curve setting of actuating drives
• Use the cursor keys to select the menu and confirm this with Enter .
i
If you keep key pressed for more than 2 seconds in the menue "Curve setting of actu-ating drives" you will cause a fault shut-down.The display shows the curve setting menu.
Fig. 5-37 curve setting menu 1 Ignition position firing-rate point 2 Set-point channel 1, oil 3 Actual value channel 1, oil 4 Set-point channel 2, air 5 Actual value channel 2, air 6 Set-point channel 3, oil 7 Actual value channel 3, oil
8 Curve data for this firing-rate point already exists
• Use the cursor keys to set the firing-rate point and confirm with Enter Set-point channel 1 is chosen (di-splayed in reverse).
• Use the cursor keys to set the channel’s actuator position.
• Use the cursor keys to switch to the next channel.
• Use the cursor keys to set actuator’s position in the selected firing-rate point.
ENGLISH
Accept or discard the entry!
The display changes to the firing-rate selection menu..
• Use key to chang to the settings menu after finishing the curve settings.
i
The following firing-rate point are available: Ignition point , 200, 250, 300, 400, 500, 600, 700, 800, 900, 999• Set your firing-rate points as described above and confirm it with Enter .
i
If you keep key pressed for more than 2 seconds in the menue "Curve setting of actu-ating drives" you will cause a fault shut-down.Set multi-stage oil operation - 1st stage
Fig. 5-38 multi-stage operation menu 1 Display 1st level
2 Set-point, air damper position 3 Actual value, air damper position
• Select the first stage and confirm this with Enter . The actuating drives move to this positions.
The set-point position for the first activated ac-tuating drive is displayed in reverse.
• Use the cursor keys to set the position of the selected actuating drive.
• Use the cursor keys to switch to a different actuating drive.
• Select Enter .
The positions for all actuating drives of the selected stage are saved.
You have the option of selecting another firing-rate point.
i
If you press the key while changing the firing-rate point, the change is discarded.Fig. 5-39 3-staged operation
i
During multi-stage operation, the following points are available:Ignition point , 1 (first stage),
Set staged oil operation - transition from first stage to second stage
Fig. 5-40 Transition from first stage to second stage 1 Display valve switch-on point, 2nd stage 2 Set-point, air damper position
3 Actual value, air damper position
• Select the set-point for the air damper position and confirm this with Enter .
The actuating drives move to this positions The set-point position for the active actua-ting drive is displayed in reverse.
ENGLISH
• Use the cursor keys to switch to a different actuating drive.
• Select Enter
The positions for all actuating drives of the selected firing-rate point are saved.
You have the option to select another firing-rate point.
i
Set the other load levels using the same procedure!Delete firing-rate curves
• In the "Settings" menu path, use the cursor keys to select the menu and confirm by pressing Enter . The display shows the "delete curves" menu.
Fig. 5-41 Delete curves menu 1 Delete curves pictogram 2 Delete curves selected 3 Confirm deletion of curves
The display shows the "confirmation prompt".
Fig. 5-42 Confirmation prompt of the delete curves menu 1 Back to previous menu
2 Delete values [selected]
3 Proceed with deletion of values
Select Enter .
The curve values are deleted.
The display shows the "values deleted" menu.
1 Values deleted UI300 display settings
Fig. 5-44 Display settings menu 1 UI300 pictogram
2 Brightness 3 Contrast
4 Waiting time for screen saver